List of Parameters
Parameters
1-255
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the first status word of faults and alarms.
Note:
Re bit 03, 07:
These bits are set if at least one fault/alarm occurs. Data is entered into the fault/alarm buffer with delay. This is the
reason that the fault/alarm buffer should only be read if, after "fault present"/"alarm present" has occurred, a change
in the buffer was also detected (r0944, r9744, r2121).
Re bit 06, 08:
These status bits are used for internal diagnostic purposes only.
Re bits 11, 12:
These status bits are used for the classification of internal alarm classes and are intended for diagnostic purposes
only on certain automation systems with SINAMICS functionality.
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
Refer to: p2155, r2197
Description:
Sets the speed threshold value for the signal "f or n comparison value reached or exceeded" (BO: r2199.1).
Dependency:
Refer to: p2142, r2199
Description:
Sets the hysteresis speed (bandwidth) for the signal "f or n / v comparison value reached or exceeded" (BO:
r2199.1).
Dependency:
Refer to: p2141, r2199
r2139.0...12
CO/BO: Status word faults/alarms 1 / ZSW fault/alarm 1
Access level:
2
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Being acknowledged
Yes
No
-
01
Acknowledgment required
Yes
No
-
03
Fault present
Yes
No
-
06
Internal message 1 present
Yes
No
-
07
Alarm present
Yes
No
-
08
Internal message 2 present
Yes
No
-
11
Alarm class bit 0
High
Low
-
12
Alarm class bit 1
High
Low
-
p2140[0...n]
Hysteresis speed 2 / n_hysteresis 2
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [rpm]
300.00 [rpm]
90.00 [rpm]
p2141[0...n]
Speed threshold 1 / n_thresh val 1
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [rpm]
210000.00 [rpm]
5.00 [rpm]
p2142[0...n]
Hysteresis speed 1 / n_hysteresis 1
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [rpm]
300.00 [rpm]
2.00 [rpm]