List of Parameters
Parameters
1-99
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the normalization characteristic for the analog outputs.
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
Refer to: p0776
Notice:
This parameter is automatically overwritten when the analog output type is changed (p0776).
Note:
This parameter is automatically overwritten if p0776 (type of analog output) is changed.
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the normalization characteristic for the analog outputs.
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 1st value pair of the
characteristic.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
The unit of this parameter (V or mA) depends on the analog input type.
Refer to: p0776
Notice:
This parameter is automatically overwritten when the analog output type is changed (p0776).
Note:
This parameter is automatically overwritten if p0776 (type of analog output) is changed.
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the normalization characteristic for the analog outputs.
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
Refer to: p0776
Notice:
This parameter is automatically overwritten when the analog output type is changed (p0776).
Note:
This parameter is automatically overwritten if p0776 (type of analog output) is changed.
The parameters for the characteristic do not have a limiting effect.
p0777[0...1]
CU analog outputs characteristic value x1 / CU AO char x1
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
-1000.00 [%]
1000.00 [%]
0.00 [%]
p0778[0...1]
CU analog outputs characteristic value y1 / CU char y1
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
-20.000 [V]
20.000 [V]
0.000 [V]
p0779[0...1]
CU analog outputs characteristic value x2 / CU char x2
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
-1000.00 [%]
1000.00 [%]
100.00 [%]