List of Parameters
Parameters
1-57
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 2nd value pair of the characteristic.
Sets the second flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0367
Note:
For induction motors, p0363 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 3rd value pair of the characteristic.
Sets the third flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0368
Note:
For induction motors, p0364 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 4th value pair of the characteristic.
Sets the fourth flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0369
Note:
For induction motors, p0365 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
p0363[0...n]
Saturation characteristic flux 2 / Mot saturat.flux 2
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
10.0 [%]
300.0 [%]
85.0 [%]
p0364[0...n]
Saturation characteristic flux 3 / Mot saturat.flux 3
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
10.0 [%]
300.0 [%]
115.0 [%]
p0365[0...n]
Saturation characteristic flux 4 / Mot saturat.flux 4
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
10.0 [%]
300.0 [%]
125.0 [%]