PE6000 User Manual Description of Function Codes
159
dividing the number of pulses collected by the DI terminal by PB-07 (Number of pulses each
meter).
When the actual length PB-06 exceeds the set length in PB-05, the DO terminal allocated with
function 10 (Length reached) becomes ON.
During the fixed length control, the length reset operation can be performed via the DI terminal
allocated with function 28. For details, see the descriptions of P4-00 to P4-09.
Allocate corresponding DI terminal with function 27 (Length count input) in applications. If the
pulse frequency is high, DI5 must be used.
Function
Code
Parameter Name
Setting Range
Default
PB-08
Set count value
1–65535
1000
PB-09
Designated count value
1–65535
1000
The count value needs to be collected by DI terminal. Allocate the corresponding DI terminal
with function 25 (Counter input) in applications. If the pulse frequency is high, DI5 must be used.
When the count value reaches the set count value (PB-08), the DO terminal allocated with
function 8 (Set count value reached) becomes ON. Then the counter stops counting.
When the counting value reaches the designated counting value (PB-09), the DO terminal
allocated with function 9 (Designated count value reached) becomes ON. Then the counter
continues to count until the set count value is reached.
PB-09 should be equal to or smaller than PB-08
Figure 5-30 Reaching the set count value and designated count value
Count pulses
input
Count pulses
input
Designated count value
reached output
Set count value reached output
Count
value