Description of Function Codes PE6000 User Manual
124
Group P7: Operation Panel and Display
Function
Code
Parameter Name
Setting Range
Default
P7-01
MF.K Key function
selection
0: MF.K key disabled
1: Switchover between operation panel
control and remote command control
(terminal or communication)
2: Switchover between forward rotation
and reverse rotation
3: Forward JOG
4: Reverse JOG
0
MF.K key refers to multifunctional key. You can set the function of the MF.K key by using this
parameter. You can perform switchover by using this key both in stop or running state.
•
0: MF.K key disabled
This key is disabled.
•
1: Switchover between operation panel control and remote command control (terminal or
communication)
You can perform switchover from the current command source to the operation panel control
(local operation). If the current command source is operation panel control, this key is invalid.
•
2: Switchover between forward rotation and reverse rotation
You can change the direction of the frequency reference by using the MF.K key. It is valid only
when the current command source is operation panel control.
•
3: Forward JOG
You can perform forward JOG (FJOG) by using the MF.K key.
•
4: Reverse JOG
You can perform reverse JOG (FJOG) by using the MF.K key.
Function
Code
Parameter Name
Setting Range
Default
P7-02
STOP/RESET key
function
0: STOP/RESET key enabled only in
operation panel control
1: STOP/RESET key enabled in any
operation mode
1