PE6000 User Manual Operation, Display and Application Examples
19
PP-02 is used to determine whether group A and group U are displayed.
Function Code
Parameter Name
Setting Range
Default
PP-02
AC drive parameter
display property
Unit's digit (group U display selection)
11
0: Not display
1: Display
Ten's digit (group A display selection)
0: Not display
1: Display
3.4 Definition and Operation of the Multifunction Key (MF.K)
You can define the function (command source switchover or rotation direction switchover) of
the multifunction key in P7-01. For details, see the description of P7-01.
3.5 Viewing Status Parameters
In the stop or running state, you can press on the operation panel to display status
parameters. Whether parameters are displayed is determined by the binary bits of values
converted from the values of P7-03, P7-04, and P7-05 in the hexadecimal format.
In stop state, a total of 16 status parameters can be displayed, as listed in the following
table.
P7-05
LED display
stop
parameters
Bit00: Set frequency (Hz)
Bit01: Bus voltage (V)
Bit02: DI input status
Bit03: DO output status
Bit04: AI1 voltage (V)
Bit05: AI2 voltage (V)
Bit06: AI3 voltage (V)
Bit07: Count value
Bit08: Length value
Bit09: PLC stage
Bit10: Load speed
Bit11: PID setting
Bit12: Pulse setting
frequency (kHz)
33
☆
In running state, five running status parameters are displayed by default, and you can set
whether other parameters are displayed by setting P7-03 and P7-04, as listed in the following
table.
P7-03
LED display
running
parameters 1
Bit00: Running frequency1
(Hz)
Bit01: Set frequency (Hz)
Bit02: Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque (%
Bit07: DI input status (V)
Bit08: DO output status
Bit09: AI1 voltage (V)
Bit10: AI2 voltage (V)
Bit11: AI3 voltage (V)
Bit12: Count value
Bit13: Length value
Bit14: Load speed
display
Bit15: PID setting
1F
☆