Function Code Tables PE6000 User Manual
70
Function
Code
Parameter Name
Setting Range
Default
Propert
y
PC-39
Acceleration/deceleration
time of simple PLC
reference 10
0–3
0
☆
PC-40
Running time of simple
PLC reference 11
0.0–6553.5s (h)
0.0s(h)
☆
PC-41
Acceleration/deceleration
time of simple PLC
reference 11
0–3
0
☆
PC-42
Running time of simple
PLC reference 12
0.0–6553.5s (h)
0.0s(h)
☆
PC-43
Acceleration/deceleration
time of simple PLC
reference 12
0–3
0
☆
PC-44
Running time of simple
PLC reference 13
0.0–6553.5s (h)
0.0s(h)
☆
PC-45
Acceleration/deceleration
time of simple PLC
reference 13
0–3
0
☆
PC-46
Running time of simple
PLC reference 14
0.0–6553.5s (h)
0.0s(h)
☆
PC-47
Acceleration/deceleration
time of simple PLC
reference 14
0–3
0
☆
PC-48
Running time of simple
PLC reference 15
0.0–6553.5s (h)
0.0s(h)
☆
PC-49
Acceleration/deceleration
time of simple PLC
reference 15
0–3
0
☆
PC-50
Time unit of simple PLC
running
0: s (second)1:h (hour)
0
☆
PC-51
Reference 0 source
0: Set by PC-00
1: AI1
2: AI2
3: Keyboard potentiometer
4: Pulse setting
5: PID
6: Set by preset frequency (P0- 08),
modified via terminal UP/ DOWN
0
☆