PE6000 User Manual Description of Function Codes
111
Function
Code
Parameter Name
Setting Range
Default
P4-18
AI curve 2 minimum input
0.00 V to P4-20
0.00 V
P4-19
Corresponding setting of AI curve 2
minimum input
-100.00%–100.0%
0.0%
P4-20
AI curve 2 maximum input
P4-18 to 10.00 V
10.00 V
P4-21
Corresponding setting of AI curve 2
maximum input
-100.00%–100.0%
100.0%
P4-22
AI2 filter time
0.00–10.00s
0.10s
The method of AI3 functions is similar to that of setting AI1 function.
Function
Code
Parameter Name
Setting Range
Default
P4-28
Pulse minimum input
0.00 kHz to P4-30
0.00 kHz
P4-29
Corresponding setting of pulse
minimum input
-100.00%–100.0%
0.0%
P4-30
Pulse maximum input
P4-28 to 50.00 kHz
50.00 kHz
P4-31
Corresponding setting of pulse
maximum input
-100.00%–100.0%
100.0%
P4-32
Pulse filter time
0.00–10.00s
0.10s
These parameters are used to set the relationship between DI5 pulse frequency and
corresponding settings. The pulses can only be input by DI5. The method of setting this function is
similar to that of setting AI1 function.
Function
Code
Parameter Name
Setting Range
Default
P4-33
AI curve selection
Unit's digit (AI1 curve selection)
321
Curve 1 (2 points, see P4-13 to P4-16)
Curve 2 (2 points, see P4-18 to P4-21)
Curve 3 (2 points, see P4-23 to P4-26)
Curve 4 (4 points, see A6-00 to A6-07)
Curve 5 (4 points, see A6-08 to A6-15)
Ten's digit (AI2 curve selection)
Curve 1 to curve 5 (same as AI1)
Hundred's digit (AI3 curve selection)
Reserved
The unit's digit, ten's digit and hundred's digit of this parameter are respectively used to select