PE6000 User Manual Function Code Tables
67
Function
Code
Parameter Name
Setting Range
Default
Property
PA-22
PID initial value holding
time
0.00–650.00s
0.00s
☆
PA-23
Maximum deviation
between two PID outputs
in forward direction
0.00%–100.00%
1.00%
☆
PA-24
Maximum deviation
between two PID outputs
in reverse direction
0.00%–100.00%
1.00%
☆
PA-25
PID integral property
Unit's digit (Integral separated)
00
☆
0: Invalid
1: Valid
Ten's digit (Whether to stop integral
operation when the output reaches
the limit)
0: Continue integral operation
1: Stop integral operation
PA-26
Detection value of PID
feedback loss
0.0%: Not judging feedback loss
0.1%–100.0%
0.0%
☆
PA-27
Detection time of PID
feedback loss
0.0–20.0s
0.0s
☆
PA-28
PID operation at stop
0: No PID operation at stop 1: PID
operation at stop
0
☆
Group PB: Swing Frequency, Fixed Length and Count
PB-00
Swing frequency setting
mode
0: Relative to the central frequency
1: Relative to the maximum frequency
0
☆
PB-01
Swing frequency
amplitude
0.0%–100.0%
0.0%
☆
PB-02
Jump frequency
amplitude
0.0%–50.0%
0.0%
☆
PB-03
Swing frequency cycle
0.0–3000.0s
10.0s
☆
PB-04
Triangular wave rising
time coefficient
0.0%–100.0%
50.0%
☆
PB-05
Set length
0–65535 m
1000m
☆
PB-06
Actual length
0–65535 m
0m
☆
PB-07
Number of pulses per
meter
0.1–6553.5
100.0
☆
PB-08
Set count value
1–65535
1000
☆
PB-09
Designated count value
1–65535
1000
☆