Description of Function Codes PE6000 User Manual
174
Figure 5-32 Schematic diagram curve 4 and curve 5
When setting curve 4 and curve 5, note that the curve's minimum input voltage, inflexion 1
voltage, inflexion 2 voltage and maximum voltage must be in increment order.
F4-34 (AI curve selection) is used to select curve for AI1 to AI3.
A6-24
Jump point of AI1 input
Default
0.0%
Setting Range
-100.0%–100.0%
A6-25
Jump amplitude of AI1 input
Default
0.5%
Setting Range
0.0%–100.0%
A6-26
Jump point of AI2 input
Default
0.0%
Setting Range
-100.0%–100.0%
A6-27
Jump amplitude of AI2 input
Default
0.5%
Setting Range
0.0%–100.0%
The AI terminals (AI1 to AI2) of the PE6000 all support the corresponding setting jump function,
which fixes the AI input corresponding setting at the jump point when AI input corresponding setting
jumps around the jump range.
For example, AI1 input voltage jumps around 5.00 V and the jump range is 4.90–5.10 V. AI1
minimum input 0.00 V corresponds to 0.0% and maximum input 10.00 V corresponds to 100.0%.
The detected AI1 input corresponding setting varies between 49.0% and 51.0%.