Description of Function Codes PE6000 User Manual
164
Function
Code
Parameter Name
Setting Range
Default
PC-51
Reference 0 source
0: Set by PC-00 1: AI1
2: AI2
3: potentiometer
4: Pulse setting
5: PID
6: Set by preset frequency (P0-08),
modified via terminal UP/DOWN
0
It determines the setting channel of reference 0. You can perform convenient switchover
between the setting channels. When multi-reference or simple PLC is used as frequency source,
the switchover between two frequency sources can be realized easily.
Group PD Communication Parameters
Please refer to the
PE6000 Communication Agreement.
Group PP: User Password
PP-00
User password
Default
0
Setting Range
0–65535
If it is set to any non-zero number, the password protection function is enabled. After a
password has been set and taken effect, you must enter the correct password in order to enter the
menu. If the entered password is incorrect you cannot view or modify parameters.
If PP-00 is set to 00000, the previously set user password is cleared, and the password
protection function is disabled.
PP-01
Parameter Name
Restore default settings
0
Setting Range
0: No operation
1: Restore factory settings except motor parameters
2: Clear records
4: Restore user backup parameters
501: Back up current user parameters
1. Restore default settings except motor parameters
If PP-01 is set to 1, most function codes are restored to the default settings except motor
parameters, frequency reference resolution (P0-22), fault records, accumulative running time
(P7-09), accumulative power-on time (P7-13) and accumulative power consumption (P7-14).