Description of Function Codes PE6000 User Manual
140
P8-42
Timing function
Default
0
Setting Range
0
Disabled
1
Enabled
P8-44
Timing duration source
Default
0.0Min
Setting Range
0.0–6500.0 Min
These parameters are used to implement the AC drive timing function.
If P8-42 is set to 1, the AC drive starts to time at startup. When the set timing duration is
reached, the AC drive stops automatically and meanwhile the corresponding DO becomes ON.
The AC drive starts timing from 0 each time it starts up and the remaining timing duration can
be queried by U0-20.
The timing duration is set in P8-43 and P8-44, in unit of minute.
P8-45
AI1 input voltage lower limit
Default
3.10V
Setting Range
0.00 V to F8-46
P8-46
AI1 input voltage upper limit
Default
6.80V
Setting Range
P8-45 to 10.00 V
When the AI1 input is larger than the value of P8-46 or smaller than the value of F8-45, the
corresponding DO becomes ON, indicating that AI1 input exceeds the limit.
P8-47
Module temperature threshold
Default
75 °C