Description of Function Codes PE6000 User Manual
158
Function
Code
Parameter Name
Setting Range
Default
PB-01
Swing frequency amplitude
0.0%–100.0%
0.0%
PB-02
Jump frequency amplitude
0.0%–50.0%
0.0%
This parameter is used to determine the swing amplitude and jump frequency amplitude.
If relative to the central frequency (PB-00 = 0), the actual swing amplitude AW is the calculation
result of F0-07 (Frequency source selection) multiplied by PB-01.
If relative to the maximum frequency (PB-00 = 1), the actual swing amplitude AW is the
calculation result of F0-10 (Maximum frequency) multiplied by PB-01.
Jump frequency = Swing amplitude AW x PB-02 (Jump frequency amplitude).
If relative to the central frequency (PB-00 = 0), the jump frequency is a variable value.
If relative to the maximum frequency (PB-00 = 1), the jump frequency is a fixed value.
The swing frequency is limited by the frequency upper limit and frequency lower limit.
Function
Code
Parameter Name
Setting Range
Default
PB-03
Swing frequency cycle
0.0–3000.0s
10.0s
PB-04
Triangular wave rising time coefficient
0.0%–100.0%
50.0%
PB-03 specifies the time of a complete swing frequency cycle.
PB-04 specifies the time percentage of triangular wave rising time to PB-03 (Swing frequency
cycle).
•
Triangular wave rising time = PB-03 (Swing frequency cycle) x PB-04 (Triangular wave rising
time coefficient, unit: s)
•
Triangular wave falling time = PB-03 (Swing frequency cycle) x (1 – PB-04 Triangular wave
rising time coefficient ,unit: s)
Function
Code
Parameter Name
Setting Range
Default
PB-05
Set length
0–65535 m
1000 m
PB-06
Actual length
0–65535 m
0 m
PB-07
Number of pulses per meter
0.1–6553.5
100.0
The preceding parameters are used for fixed length control.
The length information is collected by DI terminals. PB-06 (Actual length) is calculated by