If the output current of the AC drive is equal to or less than the zero current detection level and
the duration exceeds the zero current detection delay time, the corresponding DO becomes ON.
The zero current detection is shown in the following figure.
Figure 5-21 Zero current detection
P8-36
Output overcurrent threshold
Default
200.0%
Setting Range
0.0% (no detection)
0.1%–300.0% (rated motor current)
P8-37
Output overcurrent detection
delay time
Default
0.00s
Setting Range
0.00–600.00s
If the output current of the AC drive is equal to or higher than the overcurrent threshold and the
duration exceeds the detection delay time, the corresponding DO becomes ON. The output
overcurrent detection function is shown in the following figure.
Figure 5-22 Output overcurrent detection
Output current
Zero current
detection level
P8-34
Time
Time
Zero current
detection signal
Zero current detection
delay time P8-35