PE6000 User Manual Function Code Tables
65
Function
Code
Parameter
Name
Setting Range
Default
Property
P9-47
Fault
protection
action
selection 1
Unit's digit (Motor overload, Err11)
00000
☆
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run
Ten's digit (Power input phase loss, Err12)
Hundred's digit (Power output phase loss, Err13)
Thousand's digit (External equipment Fault,
Err15)
Ten thousand's digit (Communication Fault,
Err16)
P9-54
Frequency selection for
continuing to run upon
Fault
0: Current running frequency
1: Set frequency
2: Frequency upper limit 3:
Frequency lower limit
4: Backup frequency upon
abnormality
0
☆
P9-55
Backup frequency upon
abnormality
60.0%–100.0% (maximum
frequency)
100.0%
☆
P9-59
Action selection at
instantaneous power
Failure
0: Invalid
1: Decelerate
2: Decelerate to stop
0
☆
P9-60
Action pause judging
voltage at instantaneous
power Failure
P9-62–100.0%
100.0%
☆
P9-61
Voltage rally judging time
at instantaneous power
Failure
0.00–100.00s
0.50s
☆
P9-62
Action judging voltage at
instantaneous power
Failure
60.0%–100.0% (standard bus voltage)
80.0%
☆
P9-63
Protection upon load
becoming 0
0: Disabled
1: Enabled
0
☆
P9-64
Detection level of load
becoming 0
0.0%–100.0%
10.0%
☆
P9-65
Detection time of load
becoming 0
0.0–60.0s
1.0s
☆
Group PA: PID Function
PA-00
PID setting source
0: PA-01
1: AI1
2: AI2
3: Keyboard potentiometer
4: Pulse setting (DI5)
5: Communication setting
6: Multi-reference
0
☆