PE6000 User Manual Function Code Tables
73
Function
Code
Parameter Name
Setting Range
Default
Property
A5-04
Rapid current limit
0: Disabled1: Enabled
1
☆
A5-05
Current detection
compensation
0–100
5
☆
A5-06
Undervoltage threshold
60.0%–140.0%
100.0%
☆
A5-07
SVC optimization mode
selection
0: No optimization
1: Optimization mode 1
1
☆
A5-08
Dead-zone time adjustment
100%–200%
150%
☆
A5-09
Overvoltage threshold
200.0–2500.0 V
Model
dependent
☆
Group A6: AI Curve Setting
A6-00
AI curve 4 minimum input
-10.00 V to A6-02
0.00V
☆
A6-01
Corresponding setting of AI
curve 4 minimum input
-100.0%–100.0%
0.0%
☆
A6-02
AI curve 4 inflexion 1 input
A6-00 to A6-04
3.00V
☆
A6-03
Corresponding setting of AI
curve 4 inflexion 1 input
-100.0%–100.0%
30.0%
☆
A6-04
AI curve 4 inflexion 2 input
A6-02 to A6-06
6.00V
☆
A6-05
Corresponding setting of AI
curve 4 inflexion 2 input
-100.0%–100.0%
60.0%
☆
A6-06
AI curve 4 maximum input
A6-06 to 10.00 V
10.00V
☆
A6-07
Corresponding setting of AI
curve 4 maximum input
-100.0%–100.0%
100.0%
☆
A6-08
AI curve 5 minimum input
-10.00 V to A6-10
-10.00V
☆
A6-09
Corresponding setting of AI
curve 5 minimum input
-100.0%–100.0%
-100.0%
☆
A6-10
AI curve 5 inflexion 1 input
A6-08 to A6-12
-3.00V
☆
A6-11
Corresponding setting of AI
curve 5 inflexion 1 input
-100.0%–100.0%
30.0%
☆
A6-12
AI curve 5 inflexion 2 input
A6-10 to A6-14
3.00V
☆
A6-13
Corresponding setting of AI
curve 5 inflexion 2 input
-100.0%–100.0%
30.0%
☆
A6-14
AI curve 5 maximum input
A6-12 to 10.00 V
10.00V
☆
A6-15
Corresponding setting of AI
curve 5 maximum input
-100.0%–100.0%
100.0%
☆
A6-24
Jump point of AI1 input
corresponding setting
-100.0%–100.0%
0.0%
☆