PE6000 User Manual Description of Function Codes
145
P9-07
Short-circuit to ground upon power- on
Default
1
Setting Range
0
Disabled
1
Enabled
It is used to determine whether to check the motor is short-circuited to ground at power-on of
the AC drive.
If this function is enabled, the AC drive's UVW will have voltage output a while after power-on.
P9-09
Fault auto reset times
Default
1
Setting Range
0–20
It is used to set the times of fault auto resets if this function is used. After the value is exceeded,
the AC drive will remain in the fault state.
P9-10
DO action during fault auto reset
Default
1
Setting Range
0
Not act
1
Act
It is used to decide whether the DO acts during the fault auto reset if the fault auto reset
function is selected.
P9-11
Time interval of fault auto reset
Default
1.0s
Setting Range
0.1s–100.0s
It is used to set the waiting time from the alarm of the AC drive to fault auto reset.
P9-12
Input phase loss protection/contactor
energizing protection selection
Default
1
Setting Range
0Unit's digit:
Input phase loss protection
Ten's digit:
Contactor energizing protection
0
Disabled
1
Enabled
It is used to determine whether to perform input phase loss or contactor energizing protection.
The PE6000 models only provide this function when the power is 11KW or over 11KW. This
function is disabled when the power is less than 11KW.