PE6000 User Manual Description of Function Codes
101
The following table lists the functions available for the DI terminals.
Table 6-1 Functions of DI terminals
Value
Function
Description
0
No function
Set 0 for reserved terminals to avoid malfunction.
1
Forward RUN (FWD)
The terminal is used to control forward or reverse RUN of
the AC drive.
2
Reverse RUN (FWD)
3
Three-wire system
operation control
Determine whether the operation method of AC driver is
three-wire system operation control through the DI
terminal. For details, please refer to the descriptions of
function codes P4-11 (Terminal command mode).
4
Forward JOG (FJOG)
FJOG is JOG to run forward, while FJOG is JOG to run
reverse. For details of JOG running frequency and JOG
acceleration and deceleration time, please refer to the
descriptions of function codes P8-00, P8-01 and P8-02.
5
Reverse JOG (RJOG)
6
Terminal UP
Modify the UP/DOWN command when external terminals
set the frequency. The setting frequency can be adjusted
only under digital setting.
7
Terminal DOWN
8
Coast to stop
The AC driver blocks the output, and the stop process of
the motor will not be controlled by AC driver. It is the
same as coast to stop described in P6-10.
9
Fault Reset
Operate the function using DI terminals. It is the same as
that in the keyboard, in which the remote fault reset can
be achieved.
10
RUN pause
The AC drive decelerates to stop, but the running
parameters are all memorized, such as PLC, swing
frequency and PID parameters. After this function is
disabled, the AC drive resumes its status before stop.
11
Normally open (NO)
input of external fault
If this terminal becomes ON, the AC drive reports Err15
and performs the fault protection action. For more details,
see the description of P9-47.
12
Multi-reference terminal
1
The setting of 16 speeds or 16 other references can be
implemented through combinations of 16 states of these
four terminals. For details please refer to the Appendix
table 1.
13
Multi-reference terminal
2
14
Multi-reference terminal
3
15
Multi-reference terminal
4