PE6000 User Manual Function Code Tables
61
Function
Code
Parameter Name
Setting Range
Default
Property
P8-27
Terminal JOG preferred
0: Disabled1: Enabled
0
☆
P8-28
Frequency detection
value (PDT2)
0.00 to maximum frequency
50.00 Hz
☆
P8-29
Frequency detection
hysteresis (PDT
hysteresis 2)
0.0%–100.0% (PDT2 level)
5.0%
☆
P8-30
Any frequency reaching
detection value 1
0.00 Hz to maximum frequency
50.00 Hz
☆
P8-31
Any frequency reaching
detection amplitude 1
0.0%–100.0% (maximum
frequency)
0.0%
☆
P8-32
Any frequency reaching
detection value 2
0.00 Hz to maximum frequency
50.00 Hz
☆
P8-33
Any frequency reaching
detection amplitude 2
0.0%–100.0% (maximum
frequency)
0.0%
☆
P8-34
Zero current detection
level
0.0%–300.0% (rated motor current)
5.0%
☆
P8-35
Zero current detection
delay time
0.01–600.00s
0.10s
☆
P8-36
Output overcurrent
threshold
0.0% (no detection)
0.1%–300.0% (rated motor
current)
200.0%
☆
P8-37
Output overcurrent
detection delay time
0.00–600.00s
0.00s
☆
P8-38
Any current reaching 1
0.0%–300.0% (rated motor
current)
100.0%
☆
P8-39
Any current reaching 1
amplitude
0.0%–300.0% (rated motor
current)
0.0%
☆
P8-40
Any current reaching 2
0.0%–300.0% (rated motor
current)
100.0%
☆
P8-41
Any current reaching 2
amplitude
0.0%–300.0% (rated motor
current)
0.0%
☆
P8-42
Timing function
0: Disabled
1: Enabled
0
☆
P8-44
Timing duration
0.0–6500.0 min
0.0 min
☆
P8-45
AI1 input voltage lower limit
0.00 V to P8-46
3.10 V
☆
P8-46 AI1 input voltage upper limit
P8-45 to 10.00 V
6.80 V
☆
P8-47
Module temperature
threshold
0–100°C
75°C
☆
P8-49
Wakeup frequency
Dormant frequency (P8-51) to
maximum frequency (P0-10)
0.00 Hz
☆