Description of Function Codes PE6000 User Manual
136
During acceleration, if the running frequency is smaller than the value of P8-25, acceleration
time 2 is selected. If the running frequency is larger than the value of P8-25, acceleration time 1 is
selected.
During deceleration, if the running frequency is larger than the value of P8-26, deceleration
time 1 is selected. If the running frequency is smaller than the value of P8-26, deceleration time 2 is
selected.
P8-27
Terminal JOG preferred
Default
0
Setting Range
0
Disabled
1
Enabled
It is used to set whether terminal JOG is preferred.
If terminal JOG is preferred, the AC drive switches to terminal JOG running state when there is
a terminal JOG command during the running process of the AC drive.
P8-28
Frequency switchover point
between acceleration time 1
and acceleration time 2
Default
50.00 Hz
Setting Range
0.00 Hz to maximum frequency
P8-29
Frequency switchover point
between deceleration time 1
and deceleration time 2
Default
5.0%
Setting Range
0.0%–100.0% (FDT2 level)
The frequency detection function is the same as FDT1 function. For details, refer to the
P8-25
P8-26