PE6000 User Manual Appendix B
203
Parameter
address
Parameter description
Parameter
address
Parameter description
1006H
Output torque
1016H
AI1 voltage before calibration
1007H
Running speed
1017H
AI2 voltage before calibration
1008H
DI input flag
1018H
AI3 voltage before calibration
1009H
DO output flag
1019H
linear speed
100AH
AI1 voltage
101AH
Present power-on time
100BH
AI2 voltage
101BH
Present running time
100CH
AI3 voltage
101CH
input pulse frequency, unit 1Hz
100DH
Count value input
101DH
Communication setting value
100EH
Length value input
101EH
Actual feedback speed
100FH
Load speed
101FH
Principal frequency X display
--
--
1020H
Auxiliary frequency Y display
Attention
:
Communication setting value is the percentage to the relevant value. 10000 corresponds to
100.00%, and -10000 corresponds to -100.00%.
For frequency dimension data, the figure is the percentage of relevant maximum frequency; For
torque dimension data, the figure is P2-10, A2-48,A3-48,A4-48 (the set maximum numbers
correspond to motor 1, 2, 3, 4 respectively)
Input control commands into AV drive: (write only)
Command word
address
Function
2000H
0001: forward running
0002: reverse running
0003: forward jog
0004: reverse jog
0005:free stop
0006: decelerate to stop
0007:fault reset