Description of Function Codes PE6000 User Manual
122
Function
Code
Parameter Name
Setting Range
Default
P6-10
Stop mode
0: Decelerate to top
1: Coast to stop
0
•
0: Decelerate to stop
After the stop command is enabled, the AC drive decreases the output frequency according to
the deceleration time and stops when the frequency decreases to zero.
•
1: Coast to stop
After the stop command is enabled, the AC drive immediately stops the output. The motor will
coast to stop based on the mechanical inertia.
Function
Code
Parameter Name
Setting Range
Default
P6-11
Initial frequency of stop DC braking
0.00 Hz to maximum
frequency
0.00 Hz
P6-12
Waiting time of stop DC braking
0.0–36.0s
0.0S
P6-13
Stop DC braking current
0%–100%
0%
P6-14
Stop DC braking time
0.0–36.0s
0.0s
•
Initial frequency of stop DC braking: During the process of decelerating to stop, the AC drive
starts DC braking when the running frequency is lower than the value set in P6-11.
•
Waiting time of stop DC braking: When the running frequency decreases to the initial
frequency of stop DC braking, the AC drive stops output for a certain period and then starts DC
braking. This prevents faults such as overcurrent caused due to DC braking at high speed.
•
Stop DC braking current: Ts parameter specifies the output current at DC braking and is a
percentage relative to the base value.
•
Stop DC braking time: This parameter specifies the holding time of DC braking. If it is set to 0,
DC braking is cancelled.
The stop DC braking process is shown in the following figure. Figure 5-13 Stop DC braking
process