Description of Function Codes PE6000 User Manual
88
To satisfy requirements of different applications, the PE6000 provides two output selections of
0Hz, Yes and No.
Function
Code
Parameter Name
Setting Range
Default
P0-25
Acceleration/Deceleration time
base frequency
0: Maximum frequency (P0-10)
1: Set frequency
2: 100 Hz
0
The acceleration/deceleration time indicates the time for the AC drive to increase from 0 Hz to
the frequency set in P0-25. If this parameter is set to 1, the acceleration/deceleration time is related
to the set frequency. If the set frequency changes frequently, the motor's acceleration/deceleration
also changes
Function
Code
Parameter Name
Setting Range
Default
P0-26
Base frequency for UP/DOWN
modification during running
0: Running frequency
1: Set frequency
0
This parameter is valid only when the frequency source is digital setting.
It is used to set the base frequency to be modified by using keys
and
or the terminal
UP/DOWN function. If the running frequency and set frequency are different, there will be a large
difference between the AC drive's performance during the acceleration/ deceleration process.
Function
Code
Parameter Name
Setting Range
Default
P0-27
Binding command
source to frequency
source
Unit's digit (Binding operation panel
command to frequency source)
000
0: No binding
1: Frequency source by digital setting
2: AI1
3: AI2
4: Keyboard potentiometer
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
Ten's digit (Binding terminal command to
frequency source)
0–9, same as unit's digit
Hundred's digit (Binding communication
command to frequency source)
0–9, same as unit's digit)