PE6000 User Manual Description of Function Codes
109
Figure 5-9 Setting of three-line mode 2
As shown in the preceding figure, if SB1 is ON, the AC drive starts running when SB2 is
pressed to be ON; the AC drive instructs forward rotation when K is OFF and instructs reverse
rotation when K is ON. The AC drives stops immediately after SB1 becomes OFF. During normal
startup and running, SB1 must remain ON. The AC drive's running state is determined by the final
actions of SB1, SB2 and K.
Function
Code
Parameter Name
Setting Range
Default
P4-12
Terminal UP/DOWN rate
0.01–65.535 Hz/s
1.00 Hz/s
It is used to adjust the rate of change of frequency when the frequency is adjusted by means of
terminal UP/DOWN.
•
If P0-22 (Frequency reference resolution) is 2, the setting range is 0.001–65.535 Hz/s.
•
If P0-22 (Frequency reference resolution) is 1, the setting range is 0.01–655.35 Hz/s.
Function
Code
Parameter Name
Setting Range
Default
P4-13
AI curve 1 minimum input
0.00 V to P4-15
0.00 V
P4-14
Corresponding setting of AI curve 1
minimum input
-100.00%–100.0%
0.0%
P4-15
AI curve 1 maximum input
P4-13 to 10.00 V
10.00 V
P4-16
Corresponding setting of AI curve 1
maximum input
-100.00%–100.0%
100.0%
P4-17
AI1 filter time
0.00–10.00s
0.10s
These parameters are used to define the relationship between the analog input voltage and the
PE6000