Description of Function Codes PE6000 User Manual
82
Function
Code
Parameter Name
Setting Range
Default
P0-07
Frequency source
selection
Ten's digit (X and Y operation relationship)
0
0: X+Y
1: X-Y
2: Maximum
3: Minimum
4. X×Y
It is used to select the frequency setting channel. If the frequency source involves X and Y
operation, you can set the frequency offset in P0-21 for superposition to the X and Y operation
result, flexibly satisfying various requirements.
Frequency setting based on main frequency source X and auxiliary frequency source Y
Function
Code
Parameter Name
Setting Range
Default
P0-08
Preset frequency
0.00 to maximum frequency (valid when
frequency source is digital setting)
50 Hz
If the frequency source is digital setting or terminal UP/DOWN, the value of this parameter is
the initial frequency of the AC drive (digital setting).
Frequency source
selection
Frequency source X and
Y operation selection
Setting of operation
conditions
Target running
frequency
Main frequency
source X
Auxiliary
frequency
source Y
P0-07 ten’s digit
P0-07 unit’s digit
Set frequency