PE6000 User Manual Operation, Display and Application Examples
27
3.7.1 Frequency Setting by the Main Frequency Source
There are nine setting modes of main frequency sources, digital setting (UP/DOWN
modification, non-retentive at power failure), digital setting (UP/DOWN modification, retentive at
power failure), AI1, AI2, AI3, pulse setting, multi-reference, simple PLC, and communication
setting. You can select one in P0-03.
Figure 3-15 Frequency set by the main frequency source
According to the preceding figure, the running frequency of the AC drive can be set by means
of function codes, manual adjustment, analog input, multi-speed terminal, external feedback
signal, internal PID regulator, or the host computer.
Set the corresponding function codes of each frequency setting mode, as shown in the
preceding figure.