PE6000 User Manual Description of Function Codes
141
Setting Range
0.00 V - P8-46
When the heatsink temperature of the AC drive reaches the value of this parameter, the
corresponding DO becomes ON, indicating that the module temperature reaches the threshold.
P8-49
Wakeup frequency
Default
0.00Hz
Setting Range
Dormant frequency (P8-51) to maximum
frequency (P0-10)
P8-50
Wakeup delay time
Default
0.0s
Setting Range
0.0s–6500.0s
P8-51
Dormant frequency
Default
0.00Hz
Setting Range
0.00 Hz to wakeup frequency (P8-49)
P8-52
Dormant delay time
Default
0.0%
Setting Range
0.0s–6500.0s
These parameters are used to implement the dormant and wakeup functions in the water
supply application.
When the AC drive is in running state, the AC drive enters the dormant state and stops
automatically after the dormant delay time (P8-52) if the set frequency is lower than or equal to the
dormant frequency (P8-51).
When the AC drive is in dormant state and the current running command is effective, the AC
drives starts up after the wakeup delay time (P8-50) if the set frequency is higher than or equal to
the wakeup frequency (P8-49).
Generally, set the wakeup frequency equal to or higher than the dormant frequency. If the
wakeup frequency and dormant frequency are set to 0.00Hz, the dormant and wakeup functions
are disabled.
When the dormant function is enabled, if the frequency source is PID, whether PID operation is
performed in the dormant state is determined by PA-28. In this case, select PID operation enabled
in the stop state (PA-28 = 1).
P8-53
Current running time reached
Default
0.0Min
Setting Range
0.0 Min–6500.0 Min
If the current running time reaches the value set in this parameter, the corresponding DO
becomes ON, indicating that the current running time is reached.