Description of Function Codes PE6000 User Manual
180
U0-00
Running frequency
Display Range
0.00–320.00 Hz (P0-22 = 2)
U0-01
Set frequency
0.00–3200.0 Hz (P0-22 = 1)
These two parameters display the absolute value of theoretical running frequency and set
frequency. For the actual output frequency of the AC drive, see U0-19.
U0-02
Bus voltage
Display Range
0.0–3000.0 V
0.00–3200.0 Hz (P0-22 = 1)
It displays the AC drive's bus voltage.
U0-03
Output voltage
Display Range
0–1140 V
0.00–3200.0 Hz (P0-22 = 1)
It displays the AC drive's output voltage in the running state.
U0-04
Output current
Display Range
0.00–
655.35 A (AC drive power ≤
55 kW) 0.0–6553.5 A (AC drive
power > 55 kW)
0.00–3200.0 Hz (P0-22 = 1)
It displays the AC drive's output current in the running state.
U0-05
Output power
Display Range
0–32767
0.00–3200.0 Hz (P0-22 = 1)
It displays the AC drive's output power in the running state.
U0-06
Output torque
Display Range
-200.0%–200.0%
0.00–3200.0 Hz (P0-22 = 1)
It displays the AC drive's output torque in the running state.
U0-07
DI state
Display Range
0–32767
0.00–3200.0 Hz (P0-22 = 1)
It displays the current state of DI terminals. After the value is converted into a binary number,
each bit corresponds to a DI. "1" indicates high level signal, and "0" indicates low level signal. The
corresponding relationship between bits and DIs is described in the following table.