Function Code Tables PE6000 User Manual
74
Function
Code
Parameter Name
Setting Range
Default
Property
A6-25
Jump amplitude of AI1 input
corresponding setting
0.0%–100.0%
0.5%
☆
A6-26
Jump point of AI2 input
corresponding setting
-100.0%–100.0%
0.0%
☆
A6-27
Jump amplitude of AI2 input
corresponding setting
0.0%–100.0%
0.5%
☆
Group A8: Point-point Communication
A8-00
Point-point communication
selection
0: Disabled
1: Enabled
0
☆
A8-01
Master and slave selection
0: Master
1: Slave
0
☆
A8-02
Source selection of data
from master
0: Output torque
1: Running frequency
2: Setting frequency
3: Feedback rate
011
☆
A8-03
Usage of data received by
slave
0: Torque setting
1: Frequency setting
0
☆
A8-04
Zero offset of received data
(torque)
-100.00%–100.00%
0.00%
★
A8-05
Gain of received data
(torque)
-10.00–10.00
1.00
★
A8-06
Point-point communication
interruption detection time
0.0–10.0s
1.0s
☆
A8-07
Master data sending cycle
0.001–10.000s
0.001s
☆
Group AC: AI/AO Correction
AC-00
AI1 measured voltage 1
0.500–4.000 V
Factory
corrected
☆
AC-01
AI1 displayed voltage 1
0.500–4.000 V
Factory
corrected
☆
AC-02
AI1 measured voltage 2
6.000–9.999 V
Factory
corrected
☆
AC-03
AI1 displayed voltage 2
6.000–9.999 V
Factory
corrected
☆
AC-04
AI2 measured voltage 1
0.500–4.000 V
Factory
corrected
☆
AC-05
AI2 displayed voltage 1
0.500–4.000 V
Factory
corrected
☆
AC-06
AI2 measured voltage 2
6.000–9.999 V
Factory
corrected
☆
AC-07
AI2 displayed voltage 2
6.000–9.999 V
Factory
corrected
☆