PE6000 User Manual Description of Function Codes
87
Function
Code
Parameter Name
Setting Range
Default
P0-21
Frequency offset of auxiliary frequency
source for X and Y operation
0.00 Hz to maximum
frequency (P0-10)
0.00Hz
This parameter is valid only when the frequency source is set to "X and Y operation". The final
frequency is obtained by adding the frequency offset set in this parameter to the X and Y operation
result
Function
Code
Parameter Name
Setting Range
Default
P0-22
Frequency reference resolution
1: 0.1Hz
2: 0.01Hz
2
It is used to set the resolution of all frequency-related parameters.
If the resolution is 0.1 Hz, the PE6000 can output up to 3200 Hz. If the resolution is 0.01 Hz, the
PE6000 can output up to 320.00 Hz.
Note
Modifying this parameter will make the decimal places of all frequency-related parameters
change and corresponding frequency values change.
This parameter is not resumed when factory setting is resumed.
Function
Code
Parameter Name
Setting Range
Default
P0-23
Retentive of digital setting frequency
upon power failure
0: Not retentive
1: Retentive
0
This parameter is valid only when the frequency source is digital setting.
If P0-23 is set to 0, the digital setting frequency value resumes to the value of P0-08 (Preset
frequency) after the AC drive stops. The modification by using keys and or the terminal
UP/DOWN function is cleared.
If P0-23 is set to 1, the digital setting frequency value is the set frequency at the moment when
the AC drive stops. The modification by using keys and or the terminal UP/ DOWN
function remains effective.
Function
Code
Parameter Name
Setting Range
Default
P0-24
Output selection
0: Yes
1: No
0