Model: MTS200 (1U)
Doc. Ref. no. : m08/om/201
Issue no. : 03
User’s Manual
Page 158 of 195
Page 158 of 195
e.g.: +05:30
masibusGPSDSTStartDate
.1.3.6.1.4.1.38306.3.21.0
string
[read-write]
DST start date
Max chars: 7
Format:
mm.w.d
Mm(month): 01 <= mm <= 12,
w(week): 1 to 5,
D(day of week): 0 to 6
Day 0 is a Sunday.
e.g.:05.2.4 as Thursday of 2
nd
week of May month.
masibusGPSDSTStartTime
.1.3.6.1.4.1.38306.3.22.0
string
[read-write]
DST start time on start date
Max chars: 6
Format:
hr:min
Hr: 0 to12
Min: 0 to 59
e.g. 06:30
masibusGPSDSTEndDate
.1.3.6.1.4.1.38306.3.23.0
string
[read-write]
DST end date
Max chars: 7
Format:
mm.w.d
Mm(month): 01 <= mm <= 12,
w(week): 1 to 5,
D(day of week): 0 to 6
Day 0 is a Sunday.
e.g.:05.2.4 as Thursday of 2
nd
week of May month.
masibusGPSDSTEndTime
.1.3.6.1.4.1.38306.3.24.0
string
[read-write]
DST end time on end date
Max chars: 6
Format:
hr:min
Hr: 0 to12
Min: 0 to 59
e.g. 06:30
masibusGPSIEEE1344Mode
.1.3.6.1.4.1.38306.3.25.0
Integer
[read-write]
Selection
for
IRIG-B
or
IEEE1344 output on BNC
ports
[1 / 2]
Note:
1=IRIG-B
/
2=IEEE1344
masibusGPSIRIGTimeFormat
.1.3.6.1.4.1.38306.3.26.0
Integer
[read-write]
Selection of UTC or local time
in IRIG/IEEE1344 output
[1 / 2]
Note: 1=UTC / 2=local time
SNMP Branch
: masibusGPSNetwork
Variable
OID
Data Type
[read/write]
Description [Values]
masibusGPSEth0v4DHCP
.1.3.6.1.4.1.38306.4.1.0
Integer
[read-write]
Enable DHCP on eth0 port.
[0 / 1]
Note: 0=off, 1=on