11. Maintenance and Inspection
11-46
11.2.2
Servo Drive
Servo Alarm
If the drive detects a problem, it will trigger a servo alarm and transition to the servo off state to stop. In this
case, the value of the emergency stop setting (0x2013) is used to stop the drive.
Alarm Code
Causes
Details
What to check
IPM fault
Over current
Current limit exceeded
Motor cable
error
Wiring is incorrect and check short
Replace motor cable
Encoder cable
error
Wiring is incorrect and check short
Replace encoder cable
Parameter cable
error
Motor ID [0x2000], encoder
type[0x2001], encoder form[0x2002]
setting vaule should be same with
applied to motor label.
Modifty motor label and parameter
concordantly
Check motor
phase resistor
Check if U/V/W phase
currentffset(0x2015~0x2017) is 5% or
above of the rated current, Replace
drive
Replace motor
Machine part
has problem
Determine whether there is a conflict
or binding in the equipment.
Check machine part
Drive error
If alarm continue after servo on again,
Replace drive. Because drive may
have problem.
Error by noize
Check method to improve noise of
wiring, install.
Please check condition of wiring for
FG. Match wire size of FG with wire
size of drive main circuit.
IPM temperature
surroundings
temperature
Check wherther surrounding
temperature is over 50 [
℃
]
Lower surrounding temperature
Continuous
Overload alram
Accumulated operate overload
percentage [0x2603] Checking the
load percentage is under 100%
Change drive and motor capacitiy,
Please tune gain.
Motor cable
open
Check accumulated regenerative
overload[0x2606]
Adjust regenerarion resistor
setting[0x2009]
Use external regenerarion resistor.
Drive setting
direction
Check drive setting status
Refer “2. Wiring and Joint
Drive error
If alarm continue after servo on again,
Replace drive. Because drive may
have problem.
Current offset
Motor U/V/W
phase current
offset
oversetting
Check whether the U/V/W phase
current offset [0x2015~0x2017] are 5%
of the rated current or highter.
Rerun adjusting phase current offset
Drive error
If alarm occurs continually after
adjusting offset of phase current,
please replace new drive because
drive has problem.
Continuous overload
In case of
sequent
operating that
exceed rated
Check if load which is accumulating
driving load rate[0x2603]
is below 100% when it is in constant
Change drive and motor capacitiy,
Please tune gain.
Summary of Contents for XDL-L7NH Series
Page 2: ......
Page 12: ......
Page 21: ...1 Product Configuration 1 9 1 3 2 Servo Motor Parts 80 Flange or below 130 Flange or higher ...
Page 43: ...2 Wiring and Connection 2 21 ...
Page 58: ......
Page 68: ......
Page 75: ...4 CiA402 Drive Profile 4 7 Internal Block Diagram of CSP Mode ...
Page 78: ...4 CiA402 Drive Profile 4 10 Internal Block Diagram of PP Mode ...
Page 86: ...4 CiA402 Drive Profile 4 18 Internal Block Diagram of PV Mode ...
Page 118: ...5 Drive Application Functions 5 10 ...
Page 148: ......
Page 283: ...10 Product Specifications 10 23 SGP Series APM SGP110G ...
Page 284: ...10 Product Specifications 10 24 SGP Series APM SGP150G ...
Page 288: ...10 Product Specifications 10 28 FGP Series APM FGP110G ...
Page 294: ...10 Product Specifications 10 34 XDL L7NHB150U Weight 15 5 kg including the cooling fan ...
Page 336: ...13 Appendix 13 20 5 Turn on the power again and verify if the firmware is updated ...
Page 346: ......