9. Object Dictionary
9-22
0x200F
Overload Check Base
ALL
Variable
type
Setting range
Initial
value
Unit
Accessibility
PDO
assignment
Change
attribute
Storage
UINT
10 to 120
100
%
RW
No
Always
Yes
This indicates the load factor at which operation overload starts to be accumulated. When this is set to
a value no more than 100, operation overload will start to be accumulated earlier at the set load factor
to result in early trigger of operation overload alarm (AL-21). If the heat radiation condition of the drive
is poor, configure the setting to no more than 100% to trigger an overload alarm earlier.
0x2010
Overload Warning Level
ALL
Variable
type
Setting range
Initial
value
Unit
Accessibility
PDO
assignment
Change
attribute
Storage
UINT
10 to 100
50
%
RW
No
Always
Yes
This specifies the output level of accumulated operation overload warning (W10). When the
accumulated operation overload rate (0x2603) reaches the set value, a warning will be output. With this
setting, you can identify the time when you need to take an appropriate action before an accumulated
operation overload alarm occurs.
0x2011
PWM Off Delay Time
ALL
Variable
type
Setting range
Initial
value
Unit
Accessibility
PDO
assignment
Change
attribute
Storage
UINT
0 to 1000
10
ms
RW
No
Always
Yes
This specifies the delay time until the PWM actually turns off after running servo off command. When
using a motor with a brake installed on the vertical axis, you can output the brake signal first, and then
turn off the PWM after this set time, in order to prevent it from running down along the axis.
0x2012
Dynamic Brake Control Mode
ALL
Variable
type
Setting range
Initial
value
Unit
Accessi
bility
PDO
assignment
Change
attribute
Storage
UINT
0 to 3
0
-
RW
No
Always
Yes
This specifies the control mode of the dynamic brake on servo off.
Setting
values
Description
0
Hold the dynamic brake after stopping the motor using the brake
1
Release the dynamic brake after stopping the motor using the brake
2
Release the dynamic brake after free-run stop
3
Hold the dynamic brake after free-run stop
Summary of Contents for XDL-L7NH Series
Page 2: ......
Page 12: ......
Page 21: ...1 Product Configuration 1 9 1 3 2 Servo Motor Parts 80 Flange or below 130 Flange or higher ...
Page 43: ...2 Wiring and Connection 2 21 ...
Page 58: ......
Page 68: ......
Page 75: ...4 CiA402 Drive Profile 4 7 Internal Block Diagram of CSP Mode ...
Page 78: ...4 CiA402 Drive Profile 4 10 Internal Block Diagram of PP Mode ...
Page 86: ...4 CiA402 Drive Profile 4 18 Internal Block Diagram of PV Mode ...
Page 118: ...5 Drive Application Functions 5 10 ...
Page 148: ......
Page 283: ...10 Product Specifications 10 23 SGP Series APM SGP110G ...
Page 284: ...10 Product Specifications 10 24 SGP Series APM SGP150G ...
Page 288: ...10 Product Specifications 10 28 FGP Series APM FGP110G ...
Page 294: ...10 Product Specifications 10 34 XDL L7NHB150U Weight 15 5 kg including the cooling fan ...
Page 336: ...13 Appendix 13 20 5 Turn on the power again and verify if the firmware is updated ...
Page 346: ......