5. Drive Application Functions
5-13
How to Set User Output
1) Set the function of digital output port to be used as the user output to "Not assigned (setting value
of 0)." (Refer to Assignment of Output Signals.)
2) Set the bits (bits 16-19) corresponding to the port used as the user output for the bit mask
(0x60FE:02) to Forced Output Enabled (setting value: 1).
3) Using physical outputs (0x60FE:01), set the value corresponding to the user output for the relevant
port (bits 16-19) to 0 or 1.
Digital Output
Servo Drive
Upper Level Controller
Not assigned
Not assigned