able to withstand the large starting current. We recommend using circuit breaker with one
of the following ratings:
– 16D
– 20C
The circuit breaker is labeled with the rated current in amperes, but excluding the unit
symbol, A. Instead, the ampere figure is preceded by a letter,
B
,
C
, or
D
, which indicates
the
instantaneous tripping current
. That is the minimum value of current that causes the
circuit breaker to trip without intentional time delay. In general terms, the
C
type circuit
breaker will withstand 10 times the rated current for a short period of time. The
D
type
circuit breaker will withstand 20 times the rated current. For more information, see
standard
BS EN 60898
.
Related topics
Technical specifications, page 346
Power requirements, page 352
Simrad MF90 Installation Manual
Summary of Contents for Simrad MF90
Page 1: ...kongsberg com simrad Simrad MF90 INSTALLATION MANUAL...
Page 2: ......
Page 21: ...476671 B 19 Related topics Simrad MF90 page 13 Simrad MF90...
Page 369: ...476671 B 367 Drawing file...
Page 372: ...370 476671 B Simrad MF90 Installation Manual...
Page 375: ...476671 B 373 Drawing file...
Page 378: ...376 476671 B Simrad MF90 Installation Manual...
Page 384: ...382 476671 B Simrad MF90 Installation Manual...
Page 387: ...476671 B 385 Drawing file...
Page 390: ...388 476671 B Simrad MF90 Installation Manual...
Page 393: ...476671 B 391 Drawing file...
Page 398: ...396 476671 B Simrad MF90 Installation Manual...
Page 421: ......
Page 422: ...2022 Kongsberg Maritime ISBN 978 82 8066 240 8...
Page 423: ......
Page 425: ......
Page 426: ...Installation Manual Simrad MF90...