Installation
TRANSDUCER PNEUMATIC TUBING
Static Pressure Control Plastic Tubing
(Pneumatic Tubing)
Duct static transducers (all VAV units) and any unit with
an optional building pressure control transducer, require
pneumatic tubing to be field supplied and installed.
The “High” side
of the respective transducer must
be routed to the location in the building or ductwork
where a constant pressure is desired. Both the duct static
transducer (VAV only) and optional building pressure
transducer are mounted in the blower compartment on
the side of the electrical control box. All wiring from
the transducers is factory installed.
Duct Static Transducer
Plastic tubing (3/16" ID) must be run from the high
pressure tap of the transducer to a static pressure tap
(field supplied) in the supply duct, located at a point
where constant pressure is desired. This is normally
2/3rds of the way down the duct, before the first take
off.
Building Pressure Transducer
Plastic tubing (3/16” ID) must be run from the high
pressure tap of the building static pressure transducer
to a static pressure tap (field supplied), located in the
conditioned space. The tap should be placed in a
location where over pressurization will cause a problem,
for example, in the lobby area where excessive pressure
will cause the doors to remain open. The tap should
never be placed above the ceiling.
Static Pressure Probe Installation
On units with duct static transducers (VAV units) and
any unit with an optional building pressure, a factory
supplied Static Pressure Probe must be field installed at
the vertical post by the control compartment.
The factory supplied atmospheric pressure probe and
associated mounting hardware are shipped inside the
unit control panel. The hardware consists of a mounting
bracket and a short section of pneumatic tubing.
The
pneumatic tubing must be field installed from a factory
pressure tap (next to the mounting location for the
static pressure probe) to the atmospheric pressure
probe (see Installation Instructions, Form 100.50-
N15)
ld11072
FIGURE 27 – STATIC PRESSURE PROBE
INSTALLATION
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...