DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SETTING
LOCATION
SHOW WHEN UNIT TYPE IS
OUTSIDE AIR
MINIMUM FLOW
1
MINIMUM - DERIVED
SPAN X 5% MAXIMUM
- THE LOWER OF
DERIVED SPAN X 50%
AND OUTSIDE AIR
MAXIMUM FLOW
DERIVED
SPAN X 15%
SETPOINTS /
VENTILATION
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
OUTSIDE AIR
MAXIMUM FLOW
1
MINIMUM - OUTSIDE
AIR MINIMUM FLOW
MAXIMUM - DERIVED
FLOW
DERIVED
SPAN X 30%
SETPOINTS /
VENTILATION
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
MINIMUM OA
FLOW SETPOINT
1
0-100%
DERIVED
SPAN X 15%
SETPOINTS /
VENTILATION
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
UNIT INSTALLED
ALTITUDE
1
0-99999 FT.
0 FT.
SETPOINTS /
VENTILATION
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
VENTILATION
SYSTEM
1
USER ENABLED USER
DISABLED
USER
ENABLED
PROGRAM /
VENTILATION
DAMPER HARDWARE DOES NOT EQUAL NONE
AMS FACTOR 1
1
0.5 - 1.5
1.0
SETPOINTS /
VENTILATION
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
AMS FACTOR 2
1
0.5 - 1.5
1.0
SETPOINTS /
VENTILATION
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
TABLE 86 - VENTILATION (CONT'D)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...