AIRFLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.2
3.4
3.6
3.8
4.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
4000
867
5.4
890
5.8
912
6.2
935
6.6
958
6.9
5000
885
6.4
909
6.8
932
7.2
956
7.6
979
8.0
6000
903
7.3
928
7.8
953
8.2
976
8.7
1000
9.1
7000
914
8.3
939
8.8
963
9.4
988
9.9
1012
10.5
8000
924
9.3
949
9.9
974
10.5
999
11.2
1023
11.8
9000
934
10.6
959
11.2
983
11.9
1007
12.5
1030
13.2
10000
944
11.9
968
12.6
992
13.2
1015
13.8
1037
14.5
11000
961
13.6
984
14.2
1007
14.9
1029
15.6
1051
16.2
12000
978
15.2
1000
15.9
1022
16.6
1043
17.3
1064
18.0
13000
986
16.2
1008
16.8
1029
17.5
1050
18.2
1070
19.0
1. Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0
feet elevation.
2. Refer to Table 17 for component additions and deductions to fan performance tables.
3. BHP includes drive losses.
4. Shaded RPMs require Class II blower.
TABLE 14 - FAN PERFORMANCE - 25 TON
(CONT'D)
1,2
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...