User Interface Control Center
TABLE 84 - HEATING (CONT'D)
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT SETTING LOCATION
SHOW WHEN UNIT TYPE
IS
ADAPT MORN WARM
UP
1
USER ENABLED USER
DISABLED
USER
DISABLED
PROGRAM / HEATING
HEAT TYPE DOES NOT
EQUAL NONE AND CONSTANT
VOLUME CONTROL METHOD
DOES NOT EQUAL STAGED
NIGHT SET BACK
1
USER ENABLED USER
DISABLED
USER
DISABLED
PROGRAM / HEATING
HEAT TYPE DOES NOT EQUAL
NONE
HEAT LIMIT
TEMPERATURE
2
100.0º F - 150.0º F
130.0º F
SETPOINTS / HEATING
HEAT TYPE DOES NOT EQUAL
NONE
HEATING SAT
1
80.0º F - 115.0º F
100.0º F
SETPOINTS / HEATING
HEAT TYPE DOES NOT EQUAL
NONE, UNIT TYPE EQUALS
VARIABLE AIR VOLUM,
FLEXSYS
HW VALVE ACTION
2
DIRECT - REVERSE
DIRECT
PROGRAM / HEATING
HEATING TYPE EQUALS HOT
WATER STEAM
IST STAGE HEATING
SETPOINT
1
80.0º F - 95.0º F
85.0º F
SETPOINTS / HEATING
HEAT TYPE DOES NOT
EQUAL NONE AND UNIT TYPE
EQUALS CONSTANT VOLUME
2ND STAGE HEATING
SETPOINT
1
95.0º F - 115.0º F
100.0º F
SETPOINTS / HEATING
HEAT TYPE DOES NOT
EQUAL NONE AND UNIT TYPE
EQUALS CONSTANT VOLUME
DAILY WARM UP TIME
DAY 1
0 MIN. TO MORNING
WARM UP MAX TIME
DERIVED
HEAT TYPE DOES NOT EQUAL
NONE AND MORN WARM UP
EQUALS ENABLED
DAILY WARM UP TIME
DAY 2
0 MIN. TO MORNING
WARM UP MAX TIME
DERIVED
HEAT TYPE DOES NOT EQUAL
NONE AND MORN WARM UP
EQUALS ENABLED
DAILY WARM UP TIME
DAY 3
0 MIN. TO MORNING
WARM UP MAX TIME
DERIVED
HEAT TYPE DOES NOT EQUAL
NONE AND MORN WARM UP
EQUALS ENABLED
DAILY WARM UP TIMER
0 MIN. TO MORNING
WARM UP MAX TIME
DERIVED
HEAT TYPE DOES NOT EQUAL
NONE AND MORN WARM UP
EQUALS ENABLED
MORNING WARM UP
OPT TIME
0 MIN. TO MORNING
WARM UP MAX TIME
DERIVED
HEAT TYPE DOES NOT EQUAL
NONE AND MORN WARM UP
EQUALS ENABLED
MORNING WARM UP
MAX TIME
1
15 - 240 MIN.
120 MIN.
SETPOINTS/HEATING
HEAT TYPE DOES NOT EQUAL
NONE AND MORN WARM UP
EQUALS ENABLED
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...