172
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 86 - VENTILATION
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SETTING
LOCATION
SHOW WHEN UNIT TYPE IS
VENT SYS
STATUS
NORMAL - ACTIVE/
NORMAL - INACTIVE
/ FAULTED / USER
DISABLED / NONE
DERIVED
ALWAYS
DAMPER
HARDWARE
2
NONE / 2 POSITION/
STANDARD
STANDARD
DAMPERS
OPTIONS /
VENTILATION
ALWAYS
VENTILATION
CONTROL
1
FIXED MINIMUM /
DEMAND
FIXED
MINIMUM
OPTIONS /
VENTILATION
DAMPER HARDWARE DOES NOT EQUAL NONE
OR 2 POSITION
OA DAMPER POSITION
CURRENT
0.0 TO 100%
DERIVED
DAMPER HARDWARE DOES NOT EQUAL NONE
ACTIVE SP
0.0 TO 100%
DERIVED
IAQ DMPR AIR FLOWS
OA FLOW 1
0 TO DERIVED SPAN
DERIVED
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
OA FLOW 2
0 TO DERIVED SPAN
DERIVED
OUTSIDE AIR FLOW
TOTAL
0 TO DERIVED SPAN
DERIVED
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
ACTIVE SP
0 TO DERIVED SPAN
DERIVED
VENTILATION
DEMAND
0-100%
DERIVED
VENTILATION CONTROL EQUALS DEMAND
CO
2
LEVEL
OUTSIDE
0 TO 2000 PPM
LOOK UP
TABLE
VENTILATION CONTROL EQUALS DEMAND
INSIDE
0 TO 2000 PPM
LOOK UP
TABLE
CO
2
OFFSET
CURRENT
± 0 TO 2000 PPM
DERIVED
VENTILATION CONTROL EQUALS DEMAND
SETPOINT
1
100-1000 PPM
500 PPM
SETPOINTS /
VENTILATION
OA DAMPER
MINIMUM
POSITION
1
0 - OA DAMPER
MAXIMUM POSITION
15%
SETPOINTS /
VENTILATION
DAMPER HARDWARE DOES NOT EQUAL NONE
OR 2 POSITION DAMPER
OA DAMPER
MAXIMUM
POSITION
1
OA DAMPER MINIMUM
POSITION TO 100%
30%
SETPOINTS /
VENTILATION
DAMPER HARDWARE DOES NOT EQUAL NONE
OR 2 POSITION DAMPER
CONTINUOUS
VENT
1
USER ENABLED USER
DISABLED
USER
ENABLED
PROGRAM /
VENTILATION
UNIT TYPE EQUALS CONSTANT VOLUME
COMFORT
VENTILATION
1
USER ENABLED USER
DISABLED
USER
DISABLED
PROGRAM /
VENTILATION
UNIT TYPE EQUALS CONSTANT VOLUME
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...