TABLE 29 ELECTRICAL DATA 30 TON 208/230 VOLT WITH ERV (Cont.)
VOLT
COMPRESSORS
(EACH)
OD FAN
MOTORS
(QTY 4)
HEAT OPTION
CONV
OUTLET
SUPPLY
BLOWER
MOTOR
ERV
WHEEL
MOTOR
ERV
BLOWER
MOTOR
(QTY 2)
W/O PWRD
CONV OUTLET
WITH PWRD
CONV OUTLET
MCA
1
MAX
FUSE
2
/
BREAKER
3
SIZE
MCA
1
MAX
FUSE
2
/
BREAKER
3
SIZE
QTY RLA LRA MCC
FLA
MODEL KW STAGES AMPS FLA
HP FLA HP FLA HP FLA AMPS
AMPS
AMPS
AMPS
230-3-60
4
25 164 39
5.8
E8
80
2
185
10.4
10 28 0.25 2.5
5 15.2 253
300
263
300
7.5 22
267
300
277
300
15 42 0.25 2.5
5 15.2 270
300
281
300
7.5 22
284
300
294
300
20 54 0.25 2.5
5 15.2 285
300
296
350
7.5 22
299
350
309
350
25 68 0.25 2.5
5 15.2 303
350
313
350
7.5 22
317
350
327
350
1.
MINIMUM CIRCUIT AMPACITY.
2.
DUAL ELEMENT, TIME DELAY TYPE.
3.
HACR TYPE PER NEC.