Parameter Description and Options
MENU ITEM
DEFINITION
DAILY WARM UP TIME DAY 2
This is the Morning Warm Up time the Unit Controller recorded during the previous
day 2. This value is used to calculate the current Morning Warm initiate time for
Adaptive Morning Warm Up.
DAILY WARM UP TIME DAY 3
This is the Morning Warm Up time the Unit Controller recorded during the previous
day 3. This value is used to calculate the current Morning Warm initiate time for
Adaptive Morning Warm Up.
DAMPER HARDWARE
This parameter is programmed through the OPTIONS key and identifies the type of
ventilation system installed in the unit. The choices are None, 2 Position Damper,
Standard Dampers, Minimum IAQ, Full IAQ, 1/3-2/3 IAQ.
DEW POINT RESET
This parameter is programmed through the PROGRAM key. This function changes
the Active Supply Air Temperature to a lower value when the air beneath the floor
of a FlexSys unit approaches the dew point temperature of the air. The choices are
USER ENABLED or USER DISABLED.
DISPLAY LANGUAGE
This parameter is programmed through the OPTIONS key. This allows the user to
select the language the Unit Controller will use to display the information at the User
Interface. The choices are English or Spanish.
DISPLAY UNITS
This parameter is programmed through the OPTIONS key. This allows the user to
select which unit of measure the Unit Controller will use to display the information at
the User Interface. The choices are Imperial, metric.
DUCT PRESS TRANSDUCER SPAN
This parameter is programmed through the SETPOINTS key. This allows the use
of three different duct pressure control ranges, 0 to1.00 in-wg, 0 to 2.50 in-wg, or 0
to 5.00 in-wg.
DUCT STATIC OVER PRESSURE
This parameter is programmed through the SETPOINTS key. This sets the maximum
allowable Duct Static value before the Unit Controller lockouts the unit on an over
pressure fault.
DUCT STATIC PRESS ACTIVE SP
This is the current Duct Static Set Point that the Unit Controller is trying to
maintain.
DUCT STATIC PRESS CURRENT
This is the actual duct static pressure value.
DUCT STATIC RESET HIGH SETP
This parameter is programmed through the SETPOINTS key. This is the maximum
Duct Static Control point.
DUCT STATIC RESET LOW SETP
This parameter is programmed through the SETPOINTS key. This is the minimum
Duct Static Control point.
ECONO INSTALLED
This parameter is programmed through the PROGRAM key and tells the Unit
Controller what type of economizer is installed, None, Dry Bulb, Single Enthalpy,
Dual Enthalpy.
ECONO METHOD ACTIVE
This value indicates which of the available economizer methods the Unit Controller
is using.
ECONO METHOD TO USE
This parameter is programmed through the PROGRAM key and tells the Unit
Controller which of the available economizer options to use. The choices are Dry
Bulb, Single Enthalpy, Dual Enthalpy, or Best Available.
ECONO OUTPUT FOR FAN START
This parameter is set through the SETPOINTS key and identifies the position of the
economizer damper required to turn ON the exhaust fan in an ON/OFF DAMPER
CTRL.
ECONO OUTPUT FOR FAN STOP
This parameter is set through the SETPOINTS key and identifies the position of the
economizer damper required to turn OFF the exhaust fan in an ON/OFF DAMPER
CTRL option.
TABLE 93
-
PARAMETER DEFINITIONS (CONT'D)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...