83
2
JOHNSON CONTROLS
5276178-JIM-C-0118
POWER AND CONTROL WIRING
General
Field wiring to the unit must conform to provisions of
National Electrical Code (NEC) ANSI / NFPA 70-Latest
Edition and / or local ordinances. The unit must be
electrically grounded in accordance with the NEC
and / or local codes. Voltage tolerances which must be
maintained at the compressor terminals during starting
and running conditions are indicated on the unit Rating
Plate and Table 1.
The internal wiring harnesses furnished with this unit
are an integral part of the design certified unit. Field
alteration to comply with electrical codes should not
be required. If any of the wire supplied with the unit
must be replaced, replacement wire must be of the type
shown on the wiring diagram and the same minimum
gauge as the replaced wire.
Power supply to the unit must be NEC Class 1 and must
comply with all applicable codes. A disconnect switch
must be provided (factory option available). The switch
must be separate from all other circuits. Wire entry at
knockout openings requires conduit fittings to comply
with NEC and/or Local Codes.
Refer to Figures 6, 7, 8,
and 9 for installation location of openings.
If installing a field mounted disconnect on the unit,
refer
to Figure 11 for the recommended mounting location.
Unitstrut™ or equivalent rails should be mounted as
shown to provide structure for mounting. The location
of the rails should be adjusted to fit the disconnect within
the dimensions shown. Conduit run from the disconnect
to the power entry location in the baserail should be
routed so that it does not interfere with the doors of the
unit access panels.
Use care to avoid damage when drill
-
ing holes for the disconnect mount
-
ing.
Since not all local codes allow mount
-
ing a disconnect on the unit, please
confirm compliance with local code
before mounting a disconnect on the
unit.
Electrical wiring must be sized properly to carry the
load. Each unit must be wired with a separate branch
circuit fed directly from the meter panel and properly
fused.
When connecting electrical power and
control wiring to the unit, waterproof
connectors MUST BE USED so that
water or moisture cannot be drawn
into the unit during normal operation.
The above waterproofing conditions
will also apply when installing a field-
supplied disconnect switch.
Refer to Figure 26 for typical field wiring and to the
appropriate unit wiring diagram mounted inside control
doors for control circuit and power wiring information.
Power Wiring Detail
Units are factory wired for the voltage shown on the
unit nameplate. The main power block requires copper
wires.
Refer to Electrical Data Tables 22 through 30 to
size power wiring, fuses and disconnect switch.
All field
supplied wiring, fuses and disconnects must comply
with applicable NEC codes.
Power wiring is brought into the unit through the side
of the baserail or the bottom of the unit/control box
inside the curb. The baserail has a 2-1/2” diameter
hole for field wiring and a 3-5/8” hole is provided for a
through-the-curb connection. A removable patch plate
covers both the openings.
Waterproof connections MUST be
used to ensure that water cannot pen
-
etrate the roof or roof curb.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...