180
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 89 - SERVICE MODE
DISPLAY TEXT
TYPE
ID
VALUE
RANGE
LOCATION
DESCRIPTION
DATA LOG
FORMAT
OFF
USED TO ACTIVATE THE DATA LOG
FEATURE OF THE CONTROL
DATA LOG ERROR
ERROR
DETAIL
SEE TABLE 95
DATA LOG ERROR DETAIL
(ONLY DISPLAYED WHEN ERROR IS PRESENT)
ERROR
STATE
SEE TABLE 94
DATA LOG ERROR STATE
(ONLY DISPLAYED WHEN ERROR IS PRESENT)
UPDATE FLASH
ON / OFF
USED TO UPDATE CONTROL SOFTWARE
UPDATE FLASH
ERROR
DESCRIPTION OF THE ERROR
(ONLY DISPLAYED WHEN ERROR IS PRESENT)
FACTORY RUN
TESTER
USER DISABLE /
USER ENABLE
ONLY USED FOR FACTORY RUN TEST
COMPRESSOR 1A
DIGITAL
OUTPUT
TB4-2
ON / OFF
I/O BOARD
STATUS OF THE DIGITAL OUTPUT TO
COMPRESSOR 1
COMPRESSOR 1B
DIGITAL
OUTPUT
TB4-3
ON / OFF
I/O BOARD
STATUS OF THE DIGITAL OUTPUT TO
COMPRESSOR 2
COMPRESSOR 2A
DIGITAL
OUTPUT
TB4-4
ON / OFF
I/O BOARD
STATUS OF THE DIGITAL OUTPUT TO
COMPRESSOR 3
COMPRESSOR 2B
DIGITAL
OUTPUT
TB4-5
ON / OFF
I/O BOARD
STATUS OF THE DIGITAL OUTPUT TO
COMPRESSOR 4
COMPRESSOR 3A
DIGITAL
OUTPUT
TB4-7
ON / OFF
I/O BOARD
STATUS OF THE DIGITAL OUTPUT TO
COMPRESSOR 3A
COMPRESSOR 3B
DIGITAL
OUTPUT
TB4-8
ON / OFF
I/O BOARD
STATUS OF THE DIGITAL OUTPUT TO
COMPRESSOR 3B
CONDENSER FAN
1A/1
DIGITAL
OUTPUT
TB4-9
ON / OFF
I/O BOARD
UNIT CONTROLLER DOES NOT CONTROL
CONDENSER FANS
CONDENSER FAN
1B/2
DIGITAL
OUTPUT
TB4-10
ON / OFF
I/O BOARD
UNIT CONTROLLER DOES NOT CONTROL
CONDENSER FANS
CONDENSER FAN
2A/3
DIGITAL
OUTPUT
TB6-2
ON / OFF
I/O BOARD
UNIT CONTROLLER DOES NOT CONTROL
CONDENSER FANS
CONDENSER FAN
2B/4
DIGITAL
OUTPUT
TB6-3
ON / OFF
I/O BOARD
UNIT CONTROLLER DOES NOT CONTROL
CONDENSER FANS
CONDENSER FAN
3A/5
DIGITAL
OUTPUT
TB6-4
ON / OFF
I/O BOARD
UNIT CONTROLLER DOES NOT CONTROL
CONDENSER FANS
CONDENSER FAN
3B/6
DIGITAL
OUTPUT
TB6-5
ON / OFF
I/O BOARD
UNIT CONTROLLER DOES NOT CONTROL
CONDENSER FANS
ELECTRIC HEAT
STG 1
DIGITAL
OUTPUT
TB3-2
ON / OFF
I/O BOARD
STATUS OF ELECTRIC HEAT DIGITAL
OUTPUT TO STAGE 1
ELECTRIC HEAT
STG 2
DIGITAL
OUTPUT
TB3-3
ON / OFF
I/O BOARD
STATUS OF ELECTRIC HEAT DIGITAL
OUTPUT TO STAGE 2
ELECTRIC HEAT
STG 3
DIGITAL
OUTPUT
TB3-4
ON / OFF
I/O BOARD
STATUS OF ELECTRIC HEAT DIGITAL
OUTPUT TO STAGE 3
ELECTRIC HEAT
STG 4
DIGITAL
OUTPUT
TB3-5
ON / OFF
I/O BOARD
STATUS OF ELECTRIC HEAT DIGITAL
OUTPUT TO STAGE 4
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...