169
JOHNSON CONTROLS
5276178-JIM-C-0118
6
TABLE 84 - HEATING (CONT'D)
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT SETTING LOCATION
SHOW WHEN UNIT TYPE
IS
HEATING CONTROL
OFFSET
1º F TO 100.0º F
DERIVED
MOD FURNACE OUTPUT
RELATIVE
0.0 TO 100%
DERIVED
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
APRX RATE
37.5 TO 900.0 MBH
DERIVED
FURNACE 1A MODE
OFF / PURGE /
IGNITION / ON - LOW /
ON - HIGH / SAFETY
TRIP / SAFETY FAULT
/ SAFETY LOCKOUT /
FAULT - L/O
DERIVED
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
FURNACE 1A MODE
RELATIVE
0 TO 100%
DERIVED
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
APRX RATE
37.5 TO 150.0 MBH
DERIVED
FURNACE 1B MODE
OFF / PURGE /
IGNITION / ON /
SAFETY TRIP / SAFETY
FAULT / SAFETY
LOCKOUT / FAULT -L/O
DERIVED
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
FURNACE 1 MODE
OFF / PURGE /
IGNITION / ON-LOW /
ON - HIGH / SAFETY
TRIP / SAFETY FAULT
/ SAFETY LOCKOUT /
FAULT -L/O
DERIVED
HEAT TYPE EQUALS STAGED
GAS
FURNACE 2 MODE
OFF / PURGE /
IGNITION / ON - LOW /
ON - HIGH / SAFETY
TRIP / SAFETY FAULT
/ SAFETY LOCKOUT /
FAULT -L/O
DERIVED
GAS HEAT SIZE EQUALS 750
MBH OR 1125 MBH
FURNACE 3 MODE
OFF / PURGE /
IGNITION / ON - LOW /
ON -HIGH / SAFETY
TRIP / SAFETY FAULT
/ SAFETY LOCKOUT /
FAULT -L/O
DERIVED
GAS HEAT SIZE EQUALS 1125
MBH
HEATING SYSTEM
1
USER ENABLED USER
DISABLED
USER
ENABLED
PROGRAM / HEATING
HEAT TYPE DOES NOT EQUAL
NONE
MORNING WARM UP
1
USER ENABLED USER
DISABLED
USER
DISABLED
PROGRAM / HEATING
HEAT TYPE DOES NOT
EQUAL NONE AND CONSTANT
VOLUME CONTROL METHOD
DOES NOT EQUAL STAGED
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...