187
JOHNSON CONTROLS
5276178-JIM-C-0118
6
TABLE 89 – SERVICE MODE (CONT'D)
DISPLAY TEXT
TYPE
ID
VALUE
RANGE
LOCATION
DESCRIPTION
W2 HIGH HEAT BAS
COMMUN
PORT
P1
ON / OFF
IPU BOARD
GIVES THE STATUS OF THE
COMMUNICATED W2 HIGH HEAT
COMMAND
Y1 LOW COOL BAS
COMMUN
PORT
P1
ON / OFF
IPU BOARD
GIVES THE STATUS OF THE
COMMUNICATED Y1 LOW COOL COMMAND
Y2 HIGH COOL BAS
COMMUN
PORT
P1
ON / OFF
IPU BOARD
GIVES THE STATUS OF THE
COMMUNICATED Y2 HIGH COOL COMMAND
ZONE TEMP BAS
COMMUN
PORT
P1
-20
°F
TO 180
°F
IPU BOARD
GIVES THE ACTUAL VALUE OF THE
COMMUNICATED ZONE TEMPERATURE
FIRMWARE CRC
DERIVED
0 TO 99999
ALWAYS
THIS IS THE SIZE OF THE CODE IN THE
SOFTWARE AND IS NOT FOR FIELD USE
REAL TIME UI -
PEAK 5 SEC AND
AVERAGE
DERIVED
THE AVERAGE AND PEAK OVER THE LAST
5 SECONDS TIME USED BY THE USER
INTERFACE. THIS IS NOT FOR FIELD USE
REAL TIME UI -
LOST AND PEAK
DERIVED
THE LOST AND PEAK TIME USED BY THE
USER INTERFACE. THIS IS NOT FOR FIELD
USE
REAL TIME
CONTROL - PEAK 5
SEC AND AVERAGE
DERIVED
THE AVERAGE AND PEAK OVER THE LAST
5 SECONDS TIME USED BY THE CONTROL.
THIS IS NOT FOR FIELD USE
REAL TIME
CONTROL - LOST
AND PEAK
DERIVED
THE LOST AND PEAK TIME USED BY THE
CONTROL. THIS IS NOT FOR FIELD USE
DE MODIFIER
ADDRESS
-1 TO 41943
USED TO ENTER A SPECIFIC DE INSTANCE.
SEE SECTION 6 - COMMUNICATION
DE MODIFIER
OFFSET
-1 TO 99
USED IN COMBINATION WITH THE DE
MODIFIER ADDRESS TO ENTER A SPECIFIC
DE INSTANCE.
SEE SECTION 6 -
COMMUNICATION
P1 BAUD RATE
1200,
4800,
9600, 19200,
38400, 76800
ESTABLISHES THE COMMUNICATION BAUD
RATE FOR PORT 1
P1 MANUAL MAC
ADDRESS
-1 TO 127
ALLOWS THE MANUAL ENTRANCE OF
THE MAC ADDRESS FOR PORT 1.
SEE
SECTION 6 - COMMUNICATION
P1 PARITY
NONE, EVEN,
ODD, IGNORE
DO NOT CHANGE FROM DEFAULT VALUE
FOR BACNET
P1 PROTOCOL
BACNET, API
KEEP SETTING ON BACNET
P1 STOP BITS
1-2
DO NOT CHANGE FROM DEFAULT VALUE
FOR BACNET
P2 BAUD RATE
1200,
4800,
9600, 19200,
38400, 57600
ESTABLISHES THE COMMUNICATION BAUD
RATE FOR PORT 2
P2 MANUAL MAC
ADDRESS
-1 TO 127
ALLOWS THE MANUAL ENTRANCE OF
THE MAC ADDRESS FOR PORT 2.
SEE
SECTION 6 - COMMUNICATION
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...