TABLE 59 - HOT WATER COIL (1 ROW, 40 TON)
1
GPM
CFM
CAPACITY (MBH) AT ENTERING WATER TEMPERATURE
140 °F
160 °F
180 °F
200 °F
10
8000
102
128.8
155.8
182.9
11000
114
144.1
174.4
205.1
14000
123.2
155.9
188.8
222.1
17000
130.6
165.4
200.4
235.8
20000
136.8
173.3
210.1
247.3
20
8000
116.8
147
177.2
207.7
11000
133.2
167.7
202.3
237.2
14000
146.2
184.2
222.4
260.8
17000
157
197.9
239
280.5
20000
166.2
209.6
253.2
297.3
30
8000
122.8
154.3
185.8
217.5
11000
141.2
177.4
213.8
250.3
14000
155.9
196.1
236.4
276.9
17000
168.3
211.8
255.4
299.3
20000
179.1
225.3
271.8
318.6
40
8000
126.1
158.2
190.5
222.8
11000
145.6
182.7
220
257.5
14000
161.4
202.6
244.1
285.8
17000
174.7
219.5
264.5
309.7
20000
186.3
234.2
282.3
330.6
1. Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil
TABLE 60
-
HOT WATER COIL (2 ROW, 25 & 30 TON)
1
GPM
CFM
CAPACITY (MBH) AT ENTERING WATER TEMPERATURE
140 °F
160 °F
180 °F
200 °F
20
6000
177.5
223.8
270.4
317.3
8000
203.8
257.2
311.1
365.5
10000
224.8
284.1
343.9
404.2
12000
242.2
306.4
371.1
436.4
15000
263.6
333.8
404.6
476.1
40
6000
198.1
248.9
300.0
351.3
8000
232.2
292.0
352.2
412.7
10000
260.7
328.1
395.9
464.1
12000
285.0
359.0
433.4
508.3
15000
316.0
398.4
481.3
564.8
60
6000
206.1
258.7
311.4
364.2
8000
243.6
305.9
368.4
431.1
10000
275.3
345.9
416.8
488.0
12000
302.9
380.7
458.9
537.6
15000
338.4
425.7
513.4
601.7
80
6000
210.5
263.9
317.4
371.1
8000
249.8
313.3
377.1
441.1
10000
283.3
355.6
428.2
501.0
12000
312.7
392.7
473.0
553.6
15000
351.0
440.9
531.3
622.1
1. Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...