163
JOHNSON CONTROLS
5276178-JIM-C-0118
6
TABLE 80 - UNIT DATA
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SETTING
LOCATION
SHOW WHEN UNIT TYPE IS:
UNIT TYPE
2
CONSTANT VOLUME /
VARIABLE AIR VOLUM /
FLEXSYS
CONSTANT
VOLUME
OPTIONS /
UNIT DATA
ALWAYS
UNIT SIZE
2
50 TON
50 TON
OPTIONS /
UNIT DATA
ALWAYS SET TO 50 TON
REFRIGERANT TYPE
2
R410A
R-22
OPTIONS /
UNIT DATA
ALWAYS SET TO R410A
CONTROL METHOD
1
STAGED / WIRED ZONE TEMP /
COMM ZONE TEMP
STAGED
OPTIONS /
UNIT DATA
UNIT TYPE EQUALS CONSTANT
VOLUME
SAT RESET METHOD
1
HARDWIRED, OUTSIDE AIR,
RETURN AIR, SUPPLY FAN
SPEED
HARDWIRED INPUT
OPTIONS /
UNIT DATA
UNIT TYPE EQUALS VARIABLE
AIR VOLUM
SUPPLY AIR TEMP
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS CONSTANT
VOLUME OR VARIABLE AIR
VOLUM
ACTIVE SP
50º F TO 150º F
DERIVED
MX SUPPLY AIR TEMP
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS FLEXSYS
SETPOINT
1
50º F TO 65º F
65º F
SETOINTS/
UNIT DATA
ZONE TEMP*
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS CONSTANT
VOLUME OR VARIABLE AIR
VOLUM
OCC ZONE COOLING
SET POINT
1
OCC ZONE HEATING
SE 2.0º F
72.0º F
SETOINTS/
UNIT DATA
ZONE TEMP*
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS CONSTANT
VOLUME OR VARIABLE AIR
VOLUM
UNOCC ZONE
COOLING
SET POINT
1
UNOCC ZONE HEATING
SE 2.0º F TO 95º F
85.0º F
SETOINTS/
UNIT DATA
ZONE TEMP*
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS CONSTANT
VOLUME OR VARIABLE AIR
VOLUM
OCC ZONE HEATING
SET POINT
1
60º F TO OCC ZONE
COOLING
SETPOINT - 2.0º F
68.0º F
SETOINTS/
UNIT DATA
ZONE TEMP*
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS CONSTANT
VOLUME OR VARIABLE AIR
VOLUM
UNOCC ZONE
HEATING
SET POINT
1
50º F TO UNOCC ZONE
COOLING SETPOINT - 2.0º F
60.0º F
SETOINTS/
UNIT DATA
SMOKE PURGE
SEQ 1
1
PURGE / PRESSURIZATION /
EVACUATION
PURGE
OPTIONS /
UNIT DATA
ALWAYS
SMOKE PURGE
SEQ 2
1
PURGE / PRESSURIZATION /
EVACUATION
PRESSURIZATION
OPTIONS /
UNIT DATA
OPTION NOT AVAILABLE AS
HARD WIRED
SMOKE PURGE
SEQ 3
1
PURGE / PRESSURIZATION /
EVACUATION
EVACUATION
OPTIONS /
UNIT DATA
OPTION NOT AVAILABLE AS
HARD WIRED
DISPLAY LANGUAGE
1
ENGLISH
ENGLISH
OPTIONS /
UNIT DATA
ENGLISH ONLY AVAILABLE
DISPLAY UNITS
1
IMPERIAL / METRIC
IMPERIAL
ALWAYS
* ONLY THE ZONE TEMP SCREEN FOR THE CURRENT ACTIVE MODE WILL BE SHOWN.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...