203
JOHNSON CONTROLS
5276178-JIM-C-0118
6
BACnet NAME
USER
INTERFACE
NAME
READ/
WRITE
BACnet
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
UNIT_MODE
UNIT MODE
R
AI58
571
0 - OCCUPIED COOLING
1 - OCCUPIED COOLING LOW
2 - OCCUPIED COOLING HIGH
3 - OCCUPIED COOLING WITH BYPASS
4 - OCCUPIED COOLING WITHOUT BYPASS
5 - OCCUPIED HEATING
6 - OCCUPIED HEATING LOW
7 - OCCUPIED HEATING HIGH
8 - OCCUPIED STANDBY
9 - UNOCCUPIED COOLING
10 - UNOCCUPIED COOLING LOW
11 - UNOCCUPIED COOLING HIGH
12 - UNOCCUPIED HEATING
13 - UNOCCUPIED HEATING LOW
14 - UNOCCUPIED HEATING HIGH
15 - UNOCCUPIED STANDBY
16 - COMFORT VENT COOLING
17 - COMFORT VENT HEATING
18 - NIGHT SET BACK
19 - MORNING WARM UP
20 - POWER UP STANDBY
UNIT_STOP
UNIT STOP
R/W
AV93
1118
THIS COMMAND ALLOWS THE UNIT TO BE SHUT
DOWN THROUGH THE BAS SYSTEM (0 = NORMAL
OPERATION/ 1 = STOPPED
UNOCC_ZN_COOL
UNOCCUPIED
ZONE COOLING
R/W
AV38
1063
THE UNOCCUPIED ZONE COOLING SET POINT (F)
UNOCC_ZN_HEAT
UNOCCUPIED
ZONE HEATING
R/W
AV39
1064
THE UNOCCUPIED ZONE HEATING SET POINT (F)
UNSTABLE _SYS
UNSTABLE
SYSTEM
R
BI60
1341
THIS INDICATES A UNSTABLE SYSTEM WHEN TWO
UNITS ARE TWINNED TOGETHER AND THERE IS
A SUDDEN DROP IN SUPPLY AIR TEMPERATURE
OR FAN SPEED (0 - NORMAL OPERATION / 1 -
UNSTABLE CONDITION)
VAV_HEAT
VAV HEAT
R
BI61
1342
IDENTIFIES THE STATUS OF THE BINARY OUTPUT
TP ENERGIZE A VAV HEAT RELAY (OFF / ON)
VENT_CONTROL
VENTILATION
CONTROL
R/W
AV(BV)94
1119
A COMMUNICATED INPUT THAT ALLOWS THE
SELECTION OF THE VENTILATION FUNCTION (0 =
FIXED MINIMUM; 1= DEMAND)
VENT_DEM_OUT
VENTILATION
DEMAND P1 OUTP
R
AI59
572
THE VENTILATION OUTPUT BEING GENERATED BY
THE DEMAND VENTILATION FEATURE (%)
VENT_ENABLE
VENTILATION
ENABLE
R/W
AV95
1120
THIS COMMAND ALLOWS THE VENTILATION
FUNCTION TO BE TURNED ON OR OFF (0 = OFF /
1 = ON)
W1_LO_HEAT_B
W1 LOW HEAT BAS
R/W
AV(BV)96
1121
A COMMUNICATED VALUE THAT ALLOWS THE W1
HEAT CALL TO BE TURNED ON AND OFF (0 = OFF;
1 = ON)
W1_LOW_HEAT
W1 LOW HEAT
R
BI62
1343
IDENTIFIES THE STATUS OF THE W1 HEAT INPUT
WITH EITHER A HARDWIRED OR COMMUNCIATED
INPUT (ON / OFF)
W2_HI_HEAT_B
W2 HIGH HEAT
BAS
R/W
AV(BV)97
1122
A COMMUNICATED VALUE THAT ALLOWS THE W2
HEAT CALL TO BE TURNED ON AND OFF (0 = OFF;
1 = ON)
TABLE 90
-
BACNET MS/TP, MODBUS, BACNET IP (CONT'D)
(See notes at end of table)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...