JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 92 - N2 POINTS LIST (CONT'D)
(See notes at end of table)
B A C N E T
NAME
USER
I N T E R F A C E
NAME
READ/
WRITE
BACNET
OBJECT
TYPE
AND
INSTANCE
ENG
UNITS
N2
ADDRESS
POINTS LIST DESCRIPTION
EXH_FAN_
STAT
EXHAUST FAN
STATUS
R
BI21
0, 1
DI 14
THE STATUS OF THE EXHAUST FAN RUN
VERIFICATION CIRCUIT (0 - VERIFICATION
CIRCUIT OPEN / 1 - VERIFICATION CIRCUIT
CLOSED)
EXHAUST_OUT
EXHAUST
OUTPUT
R
AI21
%
AI 14
CONTROL OUTPUT TO THE EXHAUST DAMPER
(%)
FAN_FAULT
FAN FAULT
R
BI23
0, 1
DO 16
IDENTIFIES IF THERE IS A SUPPLY, EXHAUST, OR
RETURN FAN FAULT (0 - NO FAULT; 1 - FAULTED)
FILTER_STATS FILTER STATUS
R
BI25
0, 1
DO 17
IDENTIFIES THE STATUS OF THE BINARY DIRTY
FILTER INPUT ( 0 - NO FAULT;1 - FAULTED)
HEAT_ENT_
TMP
HEAT ENTERING
TEMP
R
AI22
DEG F
AI 15
ACTUAL TEMPERATURE OF THE AIR ENTERING
THE STAGED HEAT SECTION (F)
HEATING_SAT HEATING SAT
R/W
AV09
DEG F
AO 8
THE HEATING SAT SET POINT FOR A VAV OR
FLEXSYS UNIT (F)
HEAT_STAGES
ELECTRIC HEAT
STAGES GAS
HEAT STAGES
R
AI23
INDEX
AI 16
DERIVED VALUE SHOWING THE NUMBER OF
ELECTRIC OR STAGED GAS HEAT STAGES
AVAILABLE (1 - 7)
HEATING_VALV HEATING VALVE
R
AI24
%
AI 17
THE OUTPUT FROM THE CONTROL TO A HOT
WATER, STEAM, OR MODULATING GAS HEAT
VALVE (%)
HW_FRZ_STAT
HOT WATER FRZ
STATUS
R
BI33
0, 1
DO 18
THE STATUS OF THE FREEZESTAT CIRCUIT ON
UNITS WITH HOT WATER OR STEAM HEAT. (0 - NO
FAULT / 1 - FAULTED)
MAX_BYPASS
MAXIMUM BYPASS
R/W
AV10
%
AO 9
THE MAXIMUM ALLOWABLE SETTING FOR THE BY
PASS DAMPER IN A FLEXSYS UNIT (%)
MAX_FLOW_
DV
MAX FLOW
DEMAND
VENTILATION
R/W
AV11
CFM
AO 10
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
MECH_LCK_
TMP
MECH CLG
LOCKOUT TEMP
R/W
AV12
DEG F
AO 11
THE MINIMUM OUTDOOR TEMPERATURE AT
WHICH MECHANICAL COOLING IS ALLOWED TO
OPERATE (F)
MIN_FLOW_DV
MIN FLOW
DEMAND
VENTILATION
R/W
AV13
CFM
AO 12
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
MIXD_SAT_LIM MIXED SAT LIMIT
R/W
AV14
DEG F
AO 13
ON A FLEXSYS UNIT THIS IS THE SUPPLY AIR
SETPOINT WHEN OPERATING WITHOUT A BYPASS
DAMPER (F)
MORN_WUP_
CMD
MORNING WARM
UP CMND
R/W
AV 86
0, 1
AO 37
A BAS GENERATED COMMAND TO ALLOW THE
MORNING WARM UP FEATURE TO BE TURNED ON
AND OFF (0 = OFF / 1 = ON)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...